Wife was complaining that my UPS in the garage kept making a clunking sound and then the lights would flicker.

So I went down and watched, and sure enough the lights would flicker and the UPS would clunk. Looking over the voltages I would see a 20v drop and then it would come back. I happen to have a UPS on the 2nd leg of our box so I watched that one, and the voltage never shifted.

Turned off the breaker box, pulled the cover, pulled the breaker in question. boom, clearly it was a corroded contact causing higher resistance, and heat, and causing brownouts.

$8 later were back up and running, and I can sleep safer knowing at least THAT breaker is not going to start a fire.

all 22 comments

sorted by: hot top controversial new old
[–] 55 points 5 months ago (5 children)

Isn't it nice when the breakers, the things supposed to protect you from a fire, are the ones potentially trying to start one? But yeah, that sucks.

  • source
  • hideshow 5 child comments
  • [–] 18 points 5 months ago (4 children)

    I've heard people talk about replacing them after x number of years for this, also some folks talk about replacing electrical receptacles every 20-30 years too, as it's rated for that lifespan in your walls. I happen to be replacing mine as I go to change the color, but honestly mine are all 26 years old and I'm not sweating.

  • source
  • parent
  • hideshow 4 child comments
  • [–] [S] 13 points 5 months ago (3 children)

    if inserting a plug feels loose or if they fall out then it needs to be replaced. Otherwise its probably ok, but yes they do have a lifespan. I updated every switch and every plug in my last house because it was from the 1950's.

  • source
  • parent
  • hideshow 3 child comments
  • [+] 0 points 5 months ago (1 child)
  • [–] [S] 3 points 5 months ago

    umm.... no. Because if its loose that means the internal springs have worn out and are not firmly holding the blades on the plug. You can try a different plug and see if its just as loose in the receptacle but if it is, then you need to replace! Now i will make exceptions for Christmas lights because the blades on those are so thin and weak they often require adjustment.

  • source
  • parent
  • [–] 23 points 5 months ago (1 child)

    I thought that was a photo of a naked person straddling a bench.

  • source
  • hideshow 1 child comment
  • [–] 14 points 5 months ago (1 child)

    If one breaker is that corroded, what about the rest?

  • source
  • hideshow 1 child comment
  • [–] [S] 13 points 5 months ago

    I spot checked a few, and they looked fine but I had the same thought. Realistically though if I cant get working in the next week I am going to have to sell the house anyway so this fix was just so it wont burn down right away.

  • source
  • parent
  • [–] 9 points 5 months ago (3 children)

    $8 doesn't sound like arcfault pricing.

  • source
  • hideshow 3 child comments
  • [–] 6 points 5 months ago (2 children)

    Bingo

    If youre replacing breakers in living spaces that dont already have to be GFCIs, they should be arc faults

  • source
  • parent
  • hideshow 2 child comments
  • [–] 14 points 5 months ago (2 children)

    Lol at the old TV trope: Wife complained about a clunking noise. And I said, "Alice!"

    I went down there to investigate and it was Garfield the cat, 200 pounds and welding a strut onto a boat and then he beat me with jumper cables

  • source
  • hideshow 2 child comments
  • [–] 5 points 5 months ago

    Yer breaker broke

  • source
  • [–] 5 points 5 months ago

    Oh! I know this one! Just blow on it.

  • source
  • [–] 5 points 5 months ago

    It's nice to notice a problem, take a look, and immediately see a problem, rather than chasing an intermittent problem.

    I had an electrical issue that was an outlet that would have normal voltage until under load. Then it would tank. Turned out the neutral on one of the outlets in the chain had a contact that was loose. Took forever to find and thought I was losing my mind.

  • source
  • [–] 2 points 5 months ago (1 child)

    I just realized that UPS batteries need ro be replaced like every 3 years and I'm NOT happy about it.

  • source
  • hideshow 1 child comment