Wife was complaining that my UPS in the garage kept making a clunking sound and then the lights would flicker.

So I went down and watched, and sure enough the lights would flicker and the UPS would clunk. Looking over the voltages I would see a 20v drop and then it would come back. I happen to have a UPS on the 2nd leg of our box so I watched that one, and the voltage never shifted.

Turned off the breaker box, pulled the cover, pulled the breaker in question. boom, clearly it was a corroded contact causing higher resistance, and heat, and causing brownouts.

$8 later were back up and running, and I can sleep safer knowing at least THAT breaker is not going to start a fire.

you are viewing a single comment's thread
view the rest of the comments
[–] 18 points 5 months ago (4 children)

I've heard people talk about replacing them after x number of years for this, also some folks talk about replacing electrical receptacles every 20-30 years too, as it's rated for that lifespan in your walls. I happen to be replacing mine as I go to change the color, but honestly mine are all 26 years old and I'm not sweating.

  • source
  • parent
  • hideshow 4 child comments
  • [–] [S] 13 points 5 months ago (3 children)

    if inserting a plug feels loose or if they fall out then it needs to be replaced. Otherwise its probably ok, but yes they do have a lifespan. I updated every switch and every plug in my last house because it was from the 1950's.

  • source
  • parent
  • hideshow 3 child comments
  • [+] 0 points 5 months ago (1 child)
  • [–] [S] 3 points 5 months ago

    umm.... no. Because if its loose that means the internal springs have worn out and are not firmly holding the blades on the plug. You can try a different plug and see if its just as loose in the receptacle but if it is, then you need to replace! Now i will make exceptions for Christmas lights because the blades on those are so thin and weak they often require adjustment.

  • source
  • parent