[–] 13 points 4 months ago (1 child)

You know more about water chemistry than most of my coworkers at my power plant. I get so tired of telling them to watch the tower pH and make sure the acid is running in auto so the hypo will actually fucking do something. It's a miracle that our condenser performance isn't trashed by fouling. I've caught tower pH at fucking 9 before when it's supposed to be 7.0-7.5, and I'm trying to push for 6.8-7.2.

  • source
  • parent
  • hideshow 1 child comment
  • [–] 6 points 4 months ago

    Better than when cooling water is supplied with an expensive reverse osmosis unit which then proceeds to corrode the entire carbon steel cooling water system due to pH of 5.5 since everyone is convinced water so pure can't do any damage.