Original post (Thursday, April 30th):

Hello, c/plumbing, I'm back for another round of troubleshooting and need your help again, please.

Background: Yesterday my water heater stopped putting out hot water. Since I own my home, I decided to troubleshoot on my own before I call a professional plumber.


Ninja Edit 1 (additional background): Yesterday when we first noticed a problem, we were getting room temperature water, just warm enough to shower but still somewhat chilly, like the temp you get when you're about to run out of hot water. As of today, our "hot" water isn't even room temperature anymore, it's the same as our cold water (noticeably cooler than it was on Day 1).


(back to the original post)

What I've tried so far: With power turned off, I removed the cover panel and checked the reset button on the top thermostat, but it was not tripped (no click), so today I picked up a multimeter and tested resistance and continuity on both heating elements as demonstrated in this video. Both elements passed both tests - the resistance tests read between 12.7 and 12.9 ohms, and the continuity tests beeped. I also did a ground test, which read no resistance. So far, so good.

Where I'm stuck: At the electric panel I flipped the power back on for my water heater so I could do a voltage test at the thermostats and heating elements as demonstrated in this video. Even though my no-contact voltage tester detects hot wires (first photo), with the multimeter probes touching the topmost screws on the thermostat and/or the two screws for the heating element (second photo) my multimeter reads 0.0 volts in AC voltage mode (third photo). I've tested the multimeter on an electrical outlet and confirmed it reads 124 volts as expected (fourth photo), so I think the multimeter itself is functioning properly. I tried switching the probes, which made no difference (as expected b/c AC).

Any pointers on what I should try next? Since the multimeter doesn't read any voltage at the top thermostat, I'm not sure if this indicates an issue w/ the thermostat or if my testing process is flawed. Thank you!

Photos:

Voltage tester detects hot wires at top thermostat on water heater

Multimeter probes touching topmost screws of top thermostat on water heater

Multimeter reads zero volts at top thermostat on water heater

Multimeter reads 124 volts at electrical outlet


Ninja Edit 2 (more photos from my original testing):

I've also touched the multimeter probes to the screws on the heating element even though I originally only posted photos showing me testing the thermostat - here are the two additional photos that I should've included in the OP:

Multimeter probes touching two screws of top heating element on water heater

Multimeter reads zero volts at top heating element on water heater


Edit 3 (terminal-to-ground tested each terminal individually + more photos):

I went back out there and re-checked each terminal individually (terminal to ground) for the top and bottom thermostats and heating elements. In all cases, readings came back between 124 and 126 vac.

Multimeter probes, top thermostat, terminal 1 to ground

Multimeter readout, top thermostat, terminal 1 to ground

Multimeter probes, top thermostat, terminal 2 to ground

Multimeter readout, top thermostat, terminal 2 to ground

Multimeter probes, top heating element, terminal 1 to ground

Multimeter readout, top heating element, terminal 1 to ground

I appear to have reached the limit for image uploads on a Lemmy post, but I also terminal-to-ground tested the other terminal for the top heating element and repeated these same tests for the bottom thermostat and heating element, and all of them show between 124 and 126 vac.

Where to go from here:

From these tests I believe I can conclude that all of the components (both thermostats and heating elements) are at least receiving power from the grid, although I am perplexed as to why when I connect both multimeter probes to both terminals at the same time, the multimeter reads 0 vac, which seems different from the second video that I linked above (here's that link again).

Given these latest test results and the fact that both heating elements passed earlier continuity tests w/ the power off and wires disconnected, any ideas what to check next? Is it time to just replace all four components and see if we get our hot water back?

Edit 3.1:

I'll look again for a rogue light switch and check the individual wires and if necessary the conduit cabling as suggested in the comments, then I'll report back. I do have an appointment that I need to scurry off to at the moment, but I'll get back to this in a few hours. Thank you!


Edit 4: After testing the individual wires at the top thermostat, there appears to be a fault somewhere between the top left wire and the circuit breaker. I tested at the circuit breaker and measured normal readings (125.4, 125.7, and 250 vac), so my next step is to investigate under the conduit on top of the water heater like Cataphract suggested. I want to thank everyone for getting me to this point. Your support has been amazing, truly beyond words. I'm about to call it a night tonight, then tomorrow I'll pick up where we left off and continue updating this thread. Thanks again!


Edit 5 (Tuesday, May 5th - after being visited by the electrician):

On Saturday w/ the power off and both wires disconnected from their respective terminals at the circuit breaker and the water heater, I checked for breaks in the wires between the circuit breaker and the water heater, which are about 20 feet apart (ordered some extension leads specifically for this test). In resistance and continuity modes the multimeter shows open line for the white wire and good line for the black wire, after which I'd reached the limits of my ability/desire to continue troubleshooting, so I called and scheduled an electrician to come out on Tuesday (today).

Fast forward to today (Tuesday), electrician comes out, I explain that my multimeter reads 0 vac at the thermostat and detects an open line on that white wire, so I believe it to be a power supply issue. He disagrees w/ my diagnosis, thinks a bad element could cause 0 vac reading at the thermostat, and recommends sending a plumber. The plumber is under the same roof as the electrician, and this company has decent ratings on Yelp, so despite my skepticism I accept his recommendation to have the plumber come out and take a look.

So the plumber is coming out later this afternoon. I'll explain the situation to him and if he agrees w/ the electrician that it's likely an issue w/ the thermostat and/or heating element, I'll let him do his thing and then either we'll have hot water (hallelujah) or we won't (boo).

Stay tuned...

Edit 5.1: Holy shit, we back, baybee let'z gooo!

Okay, so while the electrician was here, he inspected the wire connections on top of the water heater and noted that the wires were not braided, so he re-did them for me and put the caps back on. I fessed up to having disconnected them and putting them back wrong during my troubleshooting adventures. Keep in mind that at this point, I had thought the issue was with the white wire itself, and he thought the issue was one of the heating elements, so neither one of us thought to test the hot water after he tweaked that.

Fast forward 90 minutes, I go wash my hands in the bathroom, and after 10 or 15 seconds I notice the water's getting warm. I immediately run upstairs to test the shower, and holy shit, it's working! She's alive!

Literally me:

I must admit that I'm still perplexed b/c I thought I had ruled out that connection point as a possibility when I tested each end of the white wire from the circuit breaker to the top of the water heater for continuity, but if there has ever been a time when I'm glad to be wrong, this is it.

I would like to once again thank @Darkassassin07@lemmy.ca and @Cataphract@lemmy.ml for their invaluable advice and support. And I would be remiss if I didn't also thank my gf for her patience while we rode this out - in Cataphract's words, an absolute saint! 😘

you are viewing a single comment's thread
view the rest of the comments
[–] [S] 4 points 6 months ago (20 children)

Connect one probe to a known good ground. (the water pipes should be grounded if metal, the case of the heater should be grounded as well) Probe each of the terminals with the other probe to find which wire is live. (checking for voltage)

Thanks for the tip - I went back out there and with power on, I checked individually every terminal for top and bottom thermostats/elements, and in all cases the multimeter read 125.5 and 125.7 vac.

Any ideas on what I should check next?

Is there perhaps a light switch nearby that doesn’t seem to control any lights?

No rogue light switches in the vicinity.

  • source
  • parent
  • hideshow 20 child comments
  • [–] 4 points 6 months ago* (last edited 6 months ago) (19 children)

    ~125vac from every terminal, to ground?

    But still 0 volts between the top two terminals?

    That's consistent with one of the two live wires being disconnected somewhere between the heater and the breaker supplying it.

    I said earlier that for this scenario to be correct you'd expect 0 volts on one side while only having ~120 on the other, but I forgot you'd read voltage through the heating elements because the thermostats will be calling for heat and connecting everything in the heater together.

    The best way to confirm this would be to [with the breaker off] disconnect either the black or red wire from one of the top two terminals. Pull it out a bit so it won't come in contact with any metal, but you can safely probe it and the terminal it was removed from. Now turn the power back on and check voltage to ground on that wire and it's terminal.


    The black and red wires on those top two terminals you've been checking are the power comming in. Regardless of what the heater is doing, even if it's totally broken with elements rotted through, you should be seeing ~240vac between those two. And both individually should have ~120vac to ground.

    Everything I'm seeing so far tells me electric supply problem. Perhaps a switch like I mentioned, they can be in not very obvious places. Could also be a failed breaker; it should be a double pole breaker that takes up two slots in the pannel. Sometimes one side will feel squishy, like it's not closing/connecting properly.

    /edit:

    From these tests I believe I can conclude that all of the components (both thermostats and heating elements) are at least receiving power from the grid.

    While each component is receiving power, they are only receiving half of a 240v supply. Note you cannot find a voltage across any component, only voltage from ground to each component.

  • source
  • parent
  • hideshow 19 child comments
  • [–] [S] 4 points 6 months ago*

    Gotcha, I will check again for a rogue light switch and test the way you describe and report back. I have an appointment this morning that I need to get scooching for, but I'll definitely come back to this in a few hours. Thanks again.

  • source
  • parent
  • [–] [S] 2 points 6 months ago* (last edited 6 months ago) (17 children)

    I hunted for a switch again and came up empty. I also disconnected the top left wire from the terminal and re-tested. I repeated this test on the top right side (wasn't sure if it would matter).

    Latest Test Results:

    • Left wire disconnected from its terminal and right wire connected:
      • Left wire to ground: 4.65 vac
      • Left terminal to ground: 123.4 vac
    • Right wire disconnected from its terminal and left wire connected:
      • Right wire to ground: 124.3 vac
      • Right terminal to ground: 2.03 vac

    I have not opened up the silver conduit piping as Cataphract suggests, but I could use help interpreting these test results. Are they consistent w/ our hypothesis that the issue is somewhere between the circuit breaker and that first thermostat? Does it help narrow down the location of the fault at all? I feel like this indicates the fault is somewhere between the left wire and the circuit breaker, but I'm not confident about that. Thank you!

    Photos:

    Left wire disconnected

    Left wire to ground

    Left terminal to ground

    Right wire disconnected

    Right wire to ground

    Right terminal to ground

  • source
  • parent
  • hideshow 17 child comments
  • [–] 2 points 6 months ago (16 children)

    You are correct: the right wire is being supplied with 120vac, however the left wire is missing its supply voltage. (the 2-5volts you're seeing is normal, for a disconnected wire. Capacitive coupling from running beside a live wire, with no path to ground).

    There is definitely something between the heater and breaker, disconnected or burnt out.

    The next thing to test is whether the breaker is correctly supplying 240vac between its two outputs. Turn off the main breaker, remove the panel cover, turn the breaker back on and check voltage between the red and black wires comming out of the water heaters breaker.

    You should get 240vac between them, and 120vac to ground.

  • source
  • parent
  • hideshow 16 child comments
  • [–] [S] 1 point 6 months ago (15 children)

    I went out to the garage to test the circuit breaker by following this video tutorial "Checking Testing Bad Circuit Breaker" by MoreThanMaintenance, and I'm stuck. At 1:05 in the video, he shows where to touch the red and black leads. The red lead is pretty self explanatory, but for the black lead, my panel looks different from his, mine doesn't have the white neutral bar. Any idea what I should touch the black lead to instead?

    Photos:

    Panel w/ cover removed:

    Electrical panel w/ cover removed

    Water heater circuit breaker:

    Close-up showing the water heater circuit breaker

    No white neutral bars on the left side:

    Close-up showing lack of white vertical neutral bar on the left side

    White neutral bars on the right side - are these for all the circuit breakers or just the right column?

    Close-up showing white vertical neutral bar on the right side

  • source
  • parent
  • hideshow 15 child comments
  • [–] 2 points 6 months ago* (last edited 6 months ago) (14 children)

    Are you sure you're testing the correct breaker? That middle breaker is using black+white, but the wires in your heater are black+red. I'd guess it's the lower of the three large breakers.

    If that definitely is the correct breaker; that confirms there is another splice to find (switch, or junction box) between the breaker and heater.

    The water heater does not have/use a neutral wire; however the two strips of terminals towards the top on both the left and right are your neutral wires. The one on the right, lower down, with bare copper wires is your ground bar. The neutral and ground bars are directly connected together unless this is a sub pannel.

    You should be voltage testing between three points in the panel:

    • From neutral (directly behind the word water in the below pic) to one of the two breaker connections.(should be 120v)
    • From neutral to the other connection (should be 120v)
    • From one breaker connection to the other breaker connection (should be 240v. Circled in blue below.)

  • source
  • parent
  • hideshow 14 child comments
  • [–] 2 points 6 months ago (2 children)

    Typically water heaters are ran with 10/2 since a neutral isn't required unless you're doing an advanced setup. The top of the water tank under the conduit will be spliced like this picture

    The red and black are internal wiring between the top splice and thermostat

    @yo_scottie_oh@lemmy.ml I'm not sure if you missed my comment earlier above here, that video will also show in depth how to properly test the breaker inside of the box and outside of it plus goes over the do's and dont's of the procedure.

  • source
  • parent
  • hideshow 2 child comments
  • [–] [S] 2 points 6 months ago*

    Just watched that video, thanks for calling my attention back to it - it is very informative. I ran the three tests at the circuit breaker and measured 125.4, 125.7, and 250 vac, which makes me think the fault is not at the circuit breaker, which leaves one last place for me to investigate, under the conduit on top of the water heater like you suggested.

  • source
  • parent
  • [–] 2 points 6 months ago

    That's a good point. Should definitely check if that's where the white transitioned into red.

    It's another spot to check for proper voltages too.


    Side note: shame on the installing electrician for not taping the white wire with red tape to indicate it's supposed to be live and not a neutral...

  • source
  • parent
  • [–] [S] 2 points 6 months ago (10 children)

    The middle double-wide breaker (w/ white & black wires connected to it) is the correct one for the water heater. The bottom one is for the dryer. I see what you mean about there being another splice somewhere, thanks for pointing that out. Also, I'm not sure how I didn't see the silver vertical bar higher up on the left side under the word "water," thanks for pointing that out.

    For testing voltage, do I have to touch a specific point on the neutral bar or should anywhere on the neutral bar work fine?

  • source
  • parent
  • hideshow 10 child comments
  • [–] 3 points 6 months ago (9 children)

    For testing voltage, do I have to touch a specific point on the neutral bar or should anywhere on the neutral bar work fine?

    Anywhere on the neutral bar is fine.

    Assuming the voltages there read correctly: Now we're going to have to track down where that white wire transitions into a red wire.

    Did you find where that random wire heading to the drain pan and through the floor goes? Perhaps there's a float switch or moisture sensor of some kind downstairs shutting things off.

  • source
  • parent
  • hideshow 9 child comments
  • [–] [S] 2 points 6 months ago (8 children)

    I ran the three tests at the circuit breaker and measured 125.4, 125.7, and 250 vac, which makes me think the fault is not at the circuit breaker, which leaves one last place to investigate, under the conduit on top of the water heater like Cataphract suggested.

    I believe that hole in the floor next to the water heater leads down to the crawl space. The previous owners had the crawl space encapsulated, and there is a dehumidifier down there, but I'm not sure either of those cables is related to that. The black cable is an unused coax cable that comes down into the garage from a second floor bedroom and then runs horizontally along the wall into the closet where the water heater is before it goes down through the hole into the crawl space. The white cable comes from a Verizon box mounted to the wall in the garage, perhaps that's where my internet connects to the outside world, I'm not sure.

    Photos:

    Black coax cable comes down from a second floor bedroom into the garage

    Black coax cable and white Verizon cable run horizontally along the wall and into the closet where the water heater is

    Black coax cable and white Verizon cable run down through a hole in the floor and into the crawl space

  • source
  • parent
  • hideshow 8 child comments
  • [–] 2 points 6 months ago

    Ah, ok: the black and white on the floor are data cables. That explains why they're not in conduit as typically required.

    That just leaves the top of the tank as you said.

    If you are not getting the expected 240v there: there has to be another junction somewhere or the cable itself has been damaged.

    Tracing that wire to find where, is going to be a challenge unfortunately.

    Can you get a photo of the other end of the armored cable that's going into the top of the heater? You'll have to follow that, checking where it enters junction boxes for broken connections.

  • source
  • parent
  • [–] 1 point 6 months ago (5 children)

    You didn't freeze to death in a cold shower did ya?

  • source
  • parent
  • hideshow 5 child comments
  • [–] [S] 1 point 6 months ago* (last edited 6 months ago) (4 children)

    Thanks for checking in. I overnighted some extension leads for my multimeter so that I could check for a break in the white wire between the circuit breaker and the water heater, which are about 20 feet apart. Sure enough, that white wire seems to be the culprit (multimeter shows an open line in resistance and continuity modes). The other wire coming out of the circuit breaker is a good line, the fault is definitely w/ the white wire.

    Can you think of any other steps I should take to troubleshoot? I believe the next step is to start cutting into the dry wall to see where/how these wires are routed behind the scenes.

  • source
  • parent
  • hideshow 4 child comments
  • [–] 2 points 6 months ago

    You're on the right track.

    I presume you opened up the conduit connection at the top and don't have 240 up there either?

    Just going to have to follow that line back until you find the broken connection. I'm certainly curious what's happened. Let us know what you find :)

  • source
  • parent
  • [–] 1 point 6 months ago (2 children)

    Congrats on the hot water :)

    Just a litte confused reading your final edits:

    So the issue turned out to be incorrect wiring from your troubleshooting? (specifically, the connection at the top of the tank, where the armored conduit meets the internal wiring?)

    What was the original problem then. A poor connection? Had you messed with that connection before coming here for help?

  • source
  • parent
  • hideshow 2 child comments
  • [–] [S] 1 point 6 months ago* (1 child)

    Only thing that makes sense to my brain is there were actually two issues, and perhaps I resolved one while introducing another through my troubleshooting and tinkering. The electrician looked at the connections where the wire from the circuit breaker meets the internal wiring of the water heater (at the end of the armored conduit) and said something along the lines of oh these two wires weren't braided, at which point I said oh that's my bad as he was redoing those connections correctly. However, neither one of us thought to test the hot water after that b/c he thought the fault was at one of the elements, and I still thought the issue was the white wire itself. It was only when I washed my hands like an hour after he'd left that I discovered the hot water was working again.

  • source
  • parent
  • hideshow 1 child comment
  • [–] 1 point 6 months ago

    Dark covered what to do if you're not getting 240 at the top of the tank (inspect the line from tank to breaker), so I'll throw some ideas at you if you are getting 240 at the top (just so you don't have to wait for further replies and can jump on the next step and get this done). Btw, kudos to your household for being patient with this process. It's not just diagnosing, but a learning and troubleshooting process. They're a saint and let them know we all appreciate the sacrifice.


    Test the black wire coming out of the top of the tank for a break, that's the one you had the low reading on previously from your pictures. It travels from the top of the tank down to the thermostat on the left side. Make sure the wires are completely disengaged from the thermostat and not touching other wires before testing. In your picture it looks like you might be pressing the black wire against the terminal when you were testing it which would give a bad reading (hard to tell from 2d). Simple testing tutorial (3:10s long)

    If the wire is good, test the thermostats as demonstrated in this video after making sure all wires are completely out of the way. Thermostat Testing (4:25s long).

    Then test the Elements, Element Testing (2:20s long).

    I know you've done this before, but these are simplified tests and redoing/varying a test is never a bad idea. The more reasons to practice with a multimeter you have, the better you'll be as well.

    You're almost there!