Yeah the restaurant burners can hit 30KW (100,000 BTU).

  • source
  • parent
  • hideshow 3 child comments
  • [–] 7 points 1 year ago (2 children)

    But reminder gas appliances are generously only ~50% efficient, so this performance is matched with a 10-15kW induction wok, which is a hefty electrical load, but doable.

  • source
  • parent
  • hideshow 2 child comments
  • [–] 0 points 1 year ago (1 child)

    Induction isn’t 100% efficient either.

    In any case, 15kw > 60 amps on a 240V circuit. That means you need a 75-80 amp breaker. It’s pretty rare to find that in a residential setting. Even hefty car chargers use a 60 amp breaker.